MIL-PRF-8565/13A
TABLE III. Capacity performance requirements. Delete the table and insert:
"TABLE III. Capacity performance requirements.
Requirement
Discharge cutoff voltage and
Rate of discharge
Minimum time to
no.
temperature
factor
cutoff voltage
(1)
1.0C
60 minutes
18.0 V at 24 ± 3° C
(2)
1.0C
66 minutes
18.0 V at 49 ± 2° C
(3)
400 watts 1/
20 minutes
21.0 V at -18 ± 2° C
(4)
400 watts 1/
30 minutes
21.0 V at 5 ± 2° C
(5)
400 watts
4 minutes
21.0 V at -40 ± 2° C
(6)
21.0 V at 24 ± 3°C
400 watts
5 minutes
1/ During the first minute of discharge, the discharge rate shall be 425 watts. The minimum
voltage of 21.0 volts shall apply during the entire discharge period."